HZGC-1212A Transformer Oil Dga Dissolve Gas Analyzer
HZGC-1212A transformer oil dga dissolve gas analyzer using three detector process standard recommend, a sampling can complete component of dissolved gas in insulation oil (including hydrogen, oxygen, methane, ethylene, ethane, acetylene, carbon monoxide and carbon dioxide) full content analysis.

Instrument configuration
Name | Model | Number | Remark |
Gas chromatograph | HZGC-1212A | 1 platform | Standard accessories |
Detector | FID | 2 individual | Standard accessories |
TCD | 1 individual | ||
Conversion device | 1 The cover | Standard accessories | |
Chromatographic column | 1 The cover | Standard accessories | |
Chromatography workstation | Special power system | 1 The cover | Standard accessories |
Concussion instrument | 1 platform | Buy locally | |
Standard gas | 1 bottle | Buy locally | |
Gas source | Nitrogen, hydrogen, air | 1 The cover | Buy locally |
Computer printer | 1 The cover | Buy locally |
Instrument performance
The first sampling, the sample volume is 1 mL, the minimum detection concentration of transformer oil(ul/L):
Component | H2 | CO | CO2 | CH4 | C2H4 | C2H6 | C2H2 |
Minimum detectable concentration(ul/L) | 2 | 1 | 5 | 0.1 | 0.1 | 0.1 | 0.1 |
dissolved gas analyzer for transformer oil
✿Typical spectrum
retention time Component Peak height content ul/L
0.258 hydrogen 6553 949.53
0.803 methane 48374 469.23
1.275 Carbon monoxide 5113 470.40
2.283 ethylene 36020 378.21
2.725 ethane 42901 557.71
3.475 acetylene 12097 191.13
10.525 Carbon dioxide 9128 3472.29



Chú phổ biến: HZGC-1212A Transformer Oil Dga Dissolve Gas Analyzer, China, suppliers, manufacturers, price, for sale, portable transformer oil dissolved gas analyzer, dissolved gas analysis test of transformer oil, dissolved gas analyzer cost, dissolved gas analysis equipment, HZGC-1212A, online dissolved gas analyzer, transformer dga measuring equipment, hzgc1212a